APFC Panel Manufacturer in Ahmedabad, Gujarat

Accu-Panels is an APFC panel manufacturer in Ahmedabad, Gujarat, building automatic power factor control panels from 20 kVAr to 3000 kVAr for factories, commercial buildings and solar plants across India and in export markets. Every panel is sized from your own electricity bill and load data, built on the same CPRI type-tested IEC 61439 platform as our PCC and MCC panels, and routine-tested before it leaves our works.

  • CPRI type-tested platform
  • IEC 61439-1/2
  • ISO 9001:2015
  • 20–3000 kVAr
  • Standard · Detuned · Thyristor (RTPFC)
  • 16+ years of panel building

What an APFC panel does, in plain words

Motors, transformers, compressors and welding sets need two kinds of power. Active power (kW) does the real work. Reactive power (kVAr) only builds the magnetic field these machines need to run. Reactive power doesn't turn a single shaft, but it still flows through your transformer, cables and switchgear, and your DISCOM still has to supply it.

Think of a truck that leaves the depot half full of empty crates. It burns the same diesel and takes up the same road, but delivers less. A low power factor is that truck. An APFC (Automatic Power Factor Correction) panel produces the reactive power right inside your plant using capacitor banks, so the grid supply carries mostly useful power.

  • SenseA CT on the main incomer measures load current and power factor, all the time.
  • DecideThe microprocessor APFC relay compares it with the target, typically 0.99 lag.
  • SwitchIt switches capacitor steps in or out through capacitor-duty contactors or thyristors.
  • HoldPower factor stays close to unity as the load changes over the shift.
Before: 0.86
With APFC: 0.97–0.99
0.800.850.900.951.00

What a well-sized APFC panel gives you

  • No power-factor penalty on the bill, and a rebate where your tariff offers one
  • Lower kVA demand, so the same transformer and cables carry more working load
  • Lower current in cables and switchgear, which means less heating, fewer I²R losses and less voltage drop
  • Steadier voltage at motor terminals during peak production hours
  • With detuned reactors, protection of the capacitors against harmonic resonance from VFDs and UPS loads

What low power factor costs a plant in Gujarat

Gujarat's electricity tariffs, set by GERC, reward good power factor and penalise poor power factor. The exact rule depends on your DISCOM and tariff category:

State DISCOMs: DGVCL · MGVCL · PGVCL · UGVCL

HT consumers (HTP-I and similar)

  • Average PF below 90% down to 85%: a penalty of 1% of the energy charges for each 1% drop
  • Below 85%: an extra 2% for each further 1% drop
  • Above 95%: a rebate of 0.5% of energy charges for each 1% rise
  • LTMD consumers pay a reactive-energy charge on every kVArh
Torrent Power: Ahmedabad licence area

LTMD and HTMD consumers

  • A per-unit penalty for each 1% the monthly average PF falls below 90%
  • A per-unit rebate for each 1% of improvement above 90%, rising above 95%
  • Paying the penalty doesn't release you from the duty to improve PF to the regulated level
Illustrative example (state DISCOM, HT): a plant whose monthly energy charges are ₹20 lakh runs at an average PF of 0.86. That's 4 steps below 90%, so the penalty is 4% = ₹80,000 a month. With an APFC panel holding 0.97, it earns a 1% rebate (2 steps above 95%) = ₹20,000 a month. The swing is about ₹1 lakh a month, before you count the savings on kVA demand. Based on GERC tariff schedules effective 1 April 2026 (state DISCOMs, Torrent Power Ahmedabad). Tariffs are revised every year and rules differ by category; check the power-factor line on your own bill. Figures are for illustration only, not a guarantee of savings.

How much kVAr does your plant need?

The required capacitor rating is kVAr = kW × (tan φ1 − tan φ2), where φ1 is your present power-factor angle and φ2 the target. For example, a 500 kW plant at 0.80 PF needs about 500 × (0.750 − 0.142) ≈ 304 kVAr to reach 0.99. Try your own numbers:

Quick kVAr estimator

304 kVArReactive power needed today
350 kVArSuggested bank size with margin (next 25 kVAr step)

This is a first estimate only. We confirm the final rating, step sizes and the need for detuned reactors from your maximum-demand readings or a 7-day load survey.

For a deeper engineering walk-through of step sizing, harmonics and reactor selection, read our guide on APFC panel kVAr sizing and detuned reactors.

Choose the right type of APFC panel

Standard APFC

Contactor-switched

Capacitor-duty contactors switch the steps in and out as load changes. Simple, robust and economical.

Best for: steady motor loads such as textile mills, pumps, compressors and HVAC, where non-linear loads are small.

Detuned APFC

With 7% or 14% reactors

A reactor in series with each step shifts the resonance below the 5th harmonic, so the capacitors don't amplify harmonics and fail early.

Best for: plants where VFDs, UPS, rectifiers or LED drivers exceed roughly 15–20% of the load, or THD(V) is above 5%.

RTPFC

Thyristor-switched, real-time

Thyristor modules switch transient-free within one cycle, so they follow loads that change many times a minute.

Best for: welding lines, cranes, presses, rolling mills and other fast-fluctuating loads.

Solar and hybrid plants: when a plant exports power in daytime, the grid can see a very low or even leading power factor. For these sites we engineer APFC control for both leading and lagging power factor, including reactive-power support for 800 V AC string-inverter plants. See our 800V solar LT panels.

APFC panel technical specifications

ParameterAccu-Panels standard range
Design standardIEC 61439-1/2 assembly; capacitors to IEC 60831-1/2; reactors to IEC 60076-6
Rated voltage415 V AC, 3-phase, 50 Hz (capacitors rated 440 V / 480 V / 525 V for detuned banks)
Compensation range20 kVAr to 3000 kVAr, in steps of 5 / 10 / 25 / 50 / 100 kVAr
SwitchingCapacitor-duty contactors (standard) or thyristor switching modules (real-time PFC)
Harmonic mitigationDetuned reactors at 7% (189 Hz) or 14% (134 Hz)
ControllerMicroprocessor APFC relay, 6 to 14 steps, target PF 0.99 lag, Modbus communication option
ProtectionMCCB incomer; HRC fuse or MCCB per step; capacitor discharge resistors; thermostat-controlled ventilation
Degree of protectionIP42 / IP54 indoor with forced ventilation; IP55 outdoor
Short-time withstand50 kA / 65 kA for 1 s busbar system
Enclosure2.0 mm CRCA frame, 1.6 mm doors; multi-tank pre-treatment and powder coating; louvres and filters for capacitor cooling

What goes into every Accu-Panels APFC panel

Sized from your data

We size the bank from your bills, maximum-demand meter readings or a 7-day load survey, and add 10–15% for future load. Your money goes into the steps you'll actually use.

Built for heat

Capacitors age fastest when they run hot. Our panels use thermostat-controlled ventilation with louvres and filters for capacitor cooling, so they cope with Indian summers.

Proven structure

The same CPRI type-tested IEC 61439 platform as our PCC and MCC panels, made at our ISO 9001:2015 certified works in Ahmedabad.

Tested before dispatch

Every panel is routine-tested before dispatch and shipped with its routine test certificate.

How we take your APFC panel from bill to dispatch

  • Share dataSend your last 3–6 electricity bills and the main load list.
  • Size & selectWe calculate kVAr, steps and switching, and check whether harmonics call for detuned reactors.
  • ApproveYou approve the GA drawing, SLD and bill of materials.
  • Build & testWe manufacture, routine-test and dispatch your panel.

Where our APFC panels work

Textile, plastics & ceramics
Large induction-motor loads running long shifts.

Cement, steel & engineering
Crushers, mills, welding and press lines, often with RTPFC.

Pharma, chemical & food
VFD-heavy process plants that need detuned banks.

Hospitals, malls & IT parks
HVAC and UPS loads, plus DISCOM PF rebates to claim.

Solar & hybrid plants
Reactive-power support at the grid interface.

Complete LT packages
Fed from our PCC panels, alongside MCC and VFD panels.

APFC panels from Ahmedabad, for Gujarat, India and export

Our APFC panels are designed and built at our works in Kathwada GIDC, Ahmedabad. Being based in Ahmedabad keeps us close to plants across Gujarat's industrial belts: send your bill and load list and our engineers will size your panel. Beyond Gujarat, we supply APFC and LT panels across India and export to more than 10 countries, including markets in Africa and the Middle East.

Keeping an APFC panel healthy

  • Check the APFC relay display every month: is the PF holding, and are all steps switching?
  • Measure each step's capacitor current every quarter. A falling current means the capacitor is losing kVAr.
  • Clean or replace the louvre filters before summer. Heat is the biggest enemy of capacitors.
  • Run a thermal scan on busbars, fuses and contactor terminals once a year.
  • Repeat the harmonic check whenever you add VFDs, UPS or other non-linear loads.

Frequently asked questions

What does an APFC panel do?

An APFC panel continuously monitors your plant's power factor and automatically switches capacitor steps in or out to keep it near unity. This avoids utility penalties, can earn PF rebates, and reduces current, losses and voltage drop in your electrical system.

How do I calculate the kVAr my plant needs?

Use kVAr = kW × (tan φ1 − tan φ2), where φ1 is the present power-factor angle and φ2 the target. A 500 kW load at 0.80 PF needs about 304 kVAr to reach 0.99. We confirm the final rating from your maximum-demand readings or a 7-day load survey and add 10–15% for future load.

When do I need a detuned APFC panel?

When non-linear loads such as VFDs, UPS, rectifiers and LED drivers exceed roughly 15–20% of the load, or a harmonic survey shows THD(V) above 5%. Plain capacitors can resonate with harmonics and fail early. 7% or 14% detuned reactors move the resonance below the 5th harmonic.

What is the difference between an APFC and an RTPFC panel?

A standard APFC panel switches capacitor steps with capacitor-duty contactors and suits steady loads. An RTPFC (real-time power factor correction) panel uses thyristor switching that responds within one cycle without switching transients, so it suits welding, cranes, presses and other fast-changing loads.

Can an APFC panel over-correct the power factor?

Yes, if it is wrongly sized or set. At light load, too much capacitance can push the power factor leading. Correct step sizes, the right relay settings and a well-placed CT prevent this. For solar plants we provide control for both leading and lagging power factor.

Does Gujarat charge a penalty for low power factor?

Yes. Under GERC tariff schedules effective 1 April 2026, HT consumers of the state DISCOMs (DGVCL, MGVCL, PGVCL and UGVCL) pay a penalty when the average power factor falls below 90% and earn a rebate above 95%. Torrent Power's Ahmedabad tariffs for LTMD and HTMD consumers also have a penalty below 90% and a rebate above 90%. Check your own bill, because rules differ by category and are revised every year.

What decides the price of an APFC panel?

Mainly the total kVAr, the number and size of steps, standard or detuned design, contactor or thyristor switching, the capacitor technology, the incomer and metering, and the enclosure and IP rating. Share your bill and load data and we will size the panel and quote within 48 hours.

What payback can I expect from an APFC panel?

Where a DISCOM levies power-factor penalties or offers incentives, APFC panels commonly pay back within 6 to 18 months through penalty avoidance, rebates and lower kVA demand. The actual payback depends on your tariff, load pattern and present power factor.

Do you supply APFC panels for 800 V solar systems?

Yes. Reactive-power compensation for 800 V AC string-inverter plants is engineered with suitably rated capacitors and reactors, and with control for both leading and lagging power factor.

Do you supply APFC panels outside Ahmedabad and Gujarat?

Yes. We build our APFC panels in Ahmedabad and supply them across Gujarat and India. We also export LT panels to more than 10 countries, including markets in Africa and the Middle East.

Send your electricity bill. We'll size your APFC panel.

Share your last few bills and your load list. Our engineers will calculate the kVAr, recommend standard, detuned or thyristor switching, and quote within 48 hours.

Get APFC sizing & quoteCall +91 63588 01780

Related panels and guides