PCC panel full form: Power Control Centre. A PCC is the main low-voltage switchboard that takes supply from the transformer or DG set, protects it with an incoming ACB, and distributes it to the plant through MCCB and ACB outgoing feeders. It is the top of a plant's LT distribution tree.
Accu-Panels is a CPRI type-tested PCC panel manufacturer in Ahmedabad, Gujarat, building IEC 61439-2 power control centres from 100 A to 6300 A, with 50 kA to 80 kA short-time withstand and Form 1 to Form 4b internal separation. Every PCC is fabricated from laser-cut CRCA, routine-tested to IEC 61439-1 and shipped with drawings, test certificates and warranty.
- PCC full form: Power Control Centre
- 100 A – 6300 A
- 50 / 65 / 80 kA for 1 s
- Form 1 to 4b
- CPRI type-tested
- Witnessed FAT
Where the PCC sits in your plant
Tap a block to see each board's job in the LT distribution chain:
- →
- →
- →
Transformer or DG set
The incoming source, linked to the PCC by cables or a bus duct. Its rating and fault level set the PCC's incomer and busbar.
PCC: the main LT board
ACB incomers up to 6300 A, bus couplers with auto-changeover or synchronising logic, and MCCB / ACB / SFU outgoing feeders, with metering and numerical protection relays.
Sub-panels fed from the PCC
MCC panels for motors, PDBs for distribution and APFC panels for power factor correction.
Plant loads
Motors, production lines, HVAC, building floors and lighting, each protected by its own feeder.
Choosing the form of separation
Form 2b
Separates the busbars from the functional units. Suits most industrial distribution.
Form 3b
Adds separation between functional units, so one feeder can be worked on while its neighbours stay live.
Form 4b
Also separates the outgoing terminals of every unit in their own compartments. Specified by hospitals, data centres, pharma and continuous-process plants where downtime is not acceptable.
Our engineers recommend the form from your SLD and maintenance philosophy, rather than defaulting to the most expensive option.
PCC panel technical specifications
| Parameter | Accu-Panels standard range |
|---|---|
| Design standard | IEC 61439-1 / IEC 61439-2 (IS/IEC 61439); type-tested at CPRI |
| Rated voltage (Ue) | 415 V AC, 3-phase 4-wire, 50 Hz (690 V and 800 V AC variants available) |
| Rated insulation voltage (Ui) | 690 V / 1000 V |
| Main busbar (InA) | 100 A to 6300 A |
| Short-time withstand (Icw) | 50 kA, 65 kA or 80 kA for 1 s, as per the installation's fault level |
| Form of separation | Form 1, 2b, 3b, 4a or 4b per IEC 61439-2 |
| Degree of protection | IP42 / IP54 indoor; IP55 / IP65 outdoor |
| Busbars | Electrolytic copper (tin-plated on request) or aluminium; heat-shrink sleeved; SMC/DMC supports |
| Enclosure | 2.0 mm CRCA frame, 1.6 mm doors and covers; 7-tank pre-treatment and powder coating; C5 finish for coastal and solar sites |
| Construction | Fixed, semi-drawout or fully drawout; single- or double-front; front or rear cable entry |
| Switchgear | ACB incomers up to 6300 A; MCCB / ACB / SFU outgoings; bus couplers with auto-changeover or synchronising logic |
| Metering and protection | Multifunction meters, class 1 / 0.5 CTs, numerical protection relays, Modbus RTU / TCP |
| Routine tests | Dielectric test at 2.5 kV for 1 min, insulation resistance, wiring and functional checks, IP and clearance verification, torque audit on every unit |
Drawings and factory acceptance test
- Drawings for approvalGA drawing, SLD, bill of materials, general notes and control schematics before fabrication starts.
- ManufactureLaser-cut CRCA, 7-tank pre-treatment, powder coating, busbar and wiring.
- Witnessed FATDimensional and BOM check, functional and interlock checks, continuity, insulation resistance and 2.5 kV test.
- DispatchWith the routine test certificate per IEC 61439-1, drawings and warranty.
Where our PCC panels work
Industry
Main LT distribution in manufacturing plants, textile mills, pharmaceutical and chemical units.
Buildings
Commercial buildings, hospitals, hotels, malls and data centres, often with Form 4b.
Solar plants
Main PCC downstream of inverter transformers, including 800 V solar LT panels.
PCC panels from Ahmedabad, for Gujarat, India and export
Our PCC panels are built in Ahmedabad, with our main plant at Kathwada GIDC. Being close means plants and consultants across Gujarat can witness the factory acceptance test with little travel. We also supply across India and export to more than 10 countries, including Africa and the Middle East. New to the terms? Read what MCC and PCC panels are.
Frequently asked questions
What is the full form of PCC panel?
PCC stands for Power Control Centre. It is the main low-voltage switchboard that receives power from the transformer or DG set and distributes it to the plant.
What is a PCC panel used for?
A PCC panel protects the incoming supply with an ACB and distributes power to MCCs, PDBs, APFC panels and large loads through MCCB and ACB outgoing feeders.
What is the difference between PCC and MCC panels?
A PCC is the main power distribution board fed from the transformer or DG. An MCC is fed from the PCC and contains the starters and protection for the plant's motors.
Which form of separation should a PCC have?
Form 2b suits most industrial distribution, Form 3b lets one feeder be worked on while its neighbours stay live, and Form 4b is specified where downtime is not acceptable, such as hospitals, data centres and pharma plants.
What tests are done on a PCC panel before dispatch?
Routine tests to IEC 61439-1 include a dielectric test at 2.5 kV for 1 minute, insulation resistance, wiring and functional checks, IP and clearance verification and a torque audit, recorded on the routine test certificate.
Can I witness the factory acceptance test?
Yes. You or your consultant can witness the FAT before dispatch, including dimensional and bill-of-materials checks, functional and interlock checks, continuity, insulation resistance and the high-voltage test.
What rating can a PCC panel have?
Accu-Panels builds PCC panels from 100 A to 6300 A, with short-time withstand of 50 kA, 65 kA or 80 kA for 1 second.
Do you supply PCC panels outside Gujarat?
Yes. We build in Ahmedabad and supply across India, and export to more than 10 countries, including Africa and the Middle East.
Send your SLD. We'll design your PCC.
Share the transformer or DG rating, fault level and outgoing feeders, and our engineers will return a GA drawing, BOM and offer.
Get PCC panel offerCall +91 63588 01780Related panels