Electrical panels for rooftop to MW-scale solar plants
Every solar plant needs a chain of LT switchgear between the modules and the grid: array junction boxes on the DC side, AC combiner boxes and ACDBs at the inverters, an 800 V or 415 V LT panel at the inverter transformer, and metering, NVR and synchronising panels at the point of connection. Accu-Panels Energy manufactures the complete range in IP65, C5-coated enclosures on a CPRI type-tested IEC 61439 platform at its Ahmedabad works, and has supplied solar EPCs and developers across India, Africa and the Middle East for over a decade.
Electrical Control Panels
Solar Products
SOLAR ACDB DCDB
Solar Products
AC DISTRIBUTION BOARD
Solar Products
DC DISTRIBUTION BOARD
Solar Products
800V LT Panel
Solar Products
AC COMBINER BOX
Solar Products
ARRAY JUNCTION BOX
Solar Products
NVR PANEL
Solar Products
TVM PANELS
Which solar panel do you need?
| Position in the plant | Panel | Key ratings |
|---|---|---|
| PV strings → inverter (DC) | Array junction box / DC distribution board | 1000 / 1500 V DC, gPV fuses, Type 2 SPD, IP65/66 |
| Inverter cluster (AC) | AC combiner box | 415 / 800 V AC, 2–16 inputs, up to 3200 A |
| Inverter → load / grid | Solar ACDB / AC distribution board | 63 A – 6300 A, SPD, MFM, IP65 |
| Inverter transformer LV side | 800 V LT panel | 800 V AC, up to 6300 A, 50–65 kA, C5 coating |
| Grid interface protection | NVR panel | No-volt, phase-failure and reverse-power relays, up to 800 A |
| Metering | TVM panel / meter panel board | CT/PT metering, ABT / net meter provision |
| Hybrid solar + DG | Synchronising panel | DG–solar–grid parallel operation, reverse-power control |
Why solar EPCs specify Accu-Panels
- 800 V AC expertise: one of the first Indian manufacturers to build 800 V LT panels for string-inverter architecture, including a 4.2 MWp plant case study.
- CPRI type-tested design to IEC 61439 with documented short-circuit, temperature-rise, dielectric and IP tests.
- Built for the field: IP65 enclosures, C5 anti-corrosion coating, canopies, breathers and UV-stable polyester options for open sites and coastal plants — read why C5 coating matters.
- SCADA-ready: Modbus RTU / TCP metering, string monitoring and SPD status contacts as standard options.
Learn more in our guides: how ACDB and DCDB work in a solar plant, 800 V LT ACDB technical highlights and DG–solar synchronising. For a project quotation, send us your plant SLD.