LT Panel Manufacturer in Ahmedabad, Gujarat

  • Home
  • Electrical LT Panels
Quick answer

LT panel full form: Low Tension panel. An LT panel is a switchboard that receives, protects, controls and distributes electrical power below 1000 V AC: 415 V, 3-phase, 50 Hz in most Indian plants and buildings, and 690 V or 800 V AC in solar plants. It sits between the transformer or DG set and your loads.

Accu-Panels is an LT panel manufacturer in Ahmedabad, Gujarat, building CPRI type-tested power control centres, motor control centres, APFC, AMF, synchronising and distribution panels to IEC 61439-1/2. Ratings run from 100 A to 6300 A, with short-time withstand up to 85 kA for 1 s and IP42 to IP65 enclosures. Pick a panel type below, or send your single-line diagram to our engineering team for a techno-commercial offer.

  • CPRI type-tested
  • IEC 61439-1/2
  • ISO 9001:2015
  • 100–6300 A · up to 85 kA
  • Form 1 to Form 4b
  • 16+ years · 10+ export countries

LT panel or HT panel? The difference in one table

LT panelHT panel
VoltageBelow 1000 V AC: 415 V, 690 V or 800 V3.3 kV to 33 kV
Main switching deviceACB, MCCB, MCB, contactorsVacuum circuit breakers
Where it sitsAfter the transformer or DG, feeding plant loadsBefore the transformer, on the utility's incoming side
Typical panelsPCC, MCC, APFC, AMF, PDB, LDBHT VCB panels, RMUs
What we buildAll LT panels, plus the LT side of HT/LT substationsNot manufactured by us

Which LT panel does your job need?

Start with what the panel has to do. Tap a job to see the right panel type, its typical rating and where to read more:

PCC panel (power control centre)

The main LT board after the transformer or DG set, with ACB incomers and MCCB outgoing feeders.

  • Typical rating: 100 A – 6300 A, 50–85 kA
  • Often linked to the transformer by a bus duct

PCC panels →

MCC panel, drawout MCC or IMCC

Motor starters, protection and control for process plants, from simple DOL starters to drawout and intelligent MCCs with communication.

  • Typical rating: 100 A – 6300 A, Form 2b to 4b
  • VFD and soft-starter feeders where needed

MCC · Drawout MCC · IMCC · VFD panels

APFC panel

Automatic power factor correction with capacitor banks and, where harmonics are present, detuned reactors.

  • Typical rating: 20 – 3000 kVAr
  • Avoids PF penalties and can earn rebates

APFC panels and kVAr estimator →

AMF, auto changeover and synchronising panels

Automatic DG start and mains–DG transfer, or parallel operation of DG sets, grid and solar inverters.

  • AMF / changeover: 32 A – 4000 A
  • Synchronising: up to 6000 A

AMF · Auto changeover · Synchronising

800 V solar LT panels, ACDB/DCDB and EV charging panels

AC collection and DC distribution for string-inverter solar plants, and distribution and protection for DC fast-charger hubs.

  • Solar: 800 V AC / 1000–1500 V DC, IP65
  • EV charging LT panels: up to 85 kA, CPRI-tested

800V LT panel · Solar ACDB & DCDB · EV charging LT panels

PDB, LDB and feeder pillars

Sub-distribution to power, lighting and outdoor circuits across a plant, building or campus.

  • Typical rating: 63 A – 1600 A
  • Indoor boards or outdoor feeder pillars

PDB · LDB · Feeder pillar

Types of LT panels we manufacture

Panel typeFunctionTypical rating
PCC panelMain LT distribution from transformer / DG with ACB incomers and MCCB feeders100 A – 6300 A, 50–85 kA
MCC / drawout MCC / IMCCMotor starters, protection and control for process plants100 A – 6300 A, Form 2b to 4b
APFC panelAutomatic power factor correction with capacitor banks and detuned reactors20 – 3000 kVAr
AMF / auto changeoverAutomatic DG start and mains–DG transfer32 A – 4000 A
Synchronising panelParallel operation of DG sets, grid and solar invertersup to 6000 A
800 V solar LT panel / solar ACDB & DCDBAC collection and DC distribution for string-inverter solar plants800 V AC / 1000–1500 V DC, IP65
PDB, LDB, feeder pillarSub-distribution to power, lighting and outdoor circuits63 A – 1600 A
Bus ductTransformer-to-PCC and PCC-to-MCC power transfer with lower losses than cablesup to 6300 A, 65 kA
EV charging LT panelDistribution and protection for DC fast-charger hubsup to 85 kA, CPRI-tested

Form 1 to Form 4b: what “form of separation” means

IEC 61439-2 describes how a panel's inside is divided by barriers. The higher the form, the more you can work on one feeder while the others stay live, at a higher cost and size.

Form 1

No internal separation. Busbars, devices and terminals share one space. Fine for small, simple boards.

Form 2a / 2b

Busbars are separated from the functional units. In 2b, the outgoing terminals are also separated from the busbars.

Form 3a / 3b

As Form 2, plus each functional unit is separated from the others. In 3b, terminals are also separated from the busbars. Common for MCCs.

Form 4a / 4b

As Form 3, plus each unit's terminals are separated from other units' terminals. In 4b, the terminals sit in their own compartment. The choice for critical plants.

“IEC 61439 compliant” is not the same as “type-tested”. Type-tested means a representative panel of the same design was physically tested at an independent laboratory such as CPRI for short-circuit withstand, temperature rise, dielectric strength and degree of protection. “Compliant” or “as per IEC” may only mean the drawing follows the standard. Always ask for the test report. What IEC 61439 type-tested really means →

Common LT panel specifications

ParameterAccu-Panels range
Design and verificationIEC 61439-1/2 (IS/IEC 61439); design verified by CPRI type tests: short-circuit withstand, temperature rise, dielectric, degree of protection
Rated voltage415 V / 690 V / 800 V AC, 50 Hz; Ui up to 1000 V
Rated current and Icw100 A to 6300 A; 50 kA, 65 kA or 85 kA for 1 s
Form of separationForm 1 to Form 4b per IEC 61439-2
Degree of protectionIP42 / IP54 indoor, IP55 / IP65 outdoor (IEC 60529)
Enclosure and finish2.0 mm CRCA frame, 1.6 mm doors; multi-tank pre-treatment; powder coat or C5 anti-corrosion system
BusbarsElectrolytic copper or aluminium, sleeved, on SMC/DMC supports

How to specify an LT panel: 6 inputs

  1. Single-line diagram (SLD), even a hand sketch
  2. Incoming source: transformer or DG rating
  3. Fault level in kA at the panel
  4. Outgoing feeders with their ratings
  5. Site conditions: indoor or outdoor, dusty, coastal
  6. Preferred switchgear make

We return a GA drawing, bill of materials and offer. Typical delivery is 4 to 8 weeks from drawing approval, depending on panel size and switchgear availability.

LT panels built in Ahmedabad, shipped across India and abroad

Accu-Panels has built LT panels for more than 16 years from Ahmedabad, with our main plant at Kathwada GIDC. Being in Ahmedabad keeps our engineers close to plants and consultants across Gujarat. For export, we supply CE-marked LT panels to more than 10 countries, including Africa and the Middle East, with sea-worthy packing and full documentation. Read how to choose an electrical panel manufacturer before you shortlist.

Frequently asked questions

What is the full form of LT panel?

LT panel stands for Low Tension panel. It is a switchboard that receives, protects, controls and distributes electrical power below 1000 V AC, typically 415 V in Indian plants and buildings.

What is an LT panel used for?

An LT panel takes power from a transformer or DG set and distributes it safely to motors, machines, lighting and other loads, with protection, switching and metering for each circuit.

What is the difference between LT and HT panels?

LT (low-tension) panels operate below 1000 V AC, typically 415 V or 800 V. HT panels switch 3.3 kV to 33 kV using vacuum circuit breakers. Accu-Panels manufactures LT panels and the LT side of HT/LT substations.

What are the main types of LT panels?

The main types are PCC (power control centre), MCC (motor control centre), APFC (power factor correction), AMF and auto changeover, synchronising panels, PDB and LDB distribution boards, feeder pillars, and solar and EV charging LT panels.

What does Form 4b mean in an LT panel?

Form 4b is the highest form of internal separation in IEC 61439-2. Busbars, each functional unit and each unit's terminals are separated, and the terminals sit in their own compartment, so one feeder can be worked on while the others stay live.

Is “IEC 61439 compliant” the same as type-tested?

No. Type-tested means a representative panel of the same design was physically tested at an independent laboratory such as CPRI. “Compliant” may only mean the drawing follows the standard. Ask for the test report.

Which IP rating do I need for an LT panel?

IP42 or IP54 for clean indoor electrical rooms, IP55 for dusty plants, and IP65 for outdoor or washdown areas and solar sites.

What information do you need to quote an LT panel?

The single-line diagram, the incoming transformer or DG rating, the fault level at the panel, the outgoing feeders with ratings, the site conditions and your preferred switchgear make.

What is a typical delivery time for an LT panel?

4 to 8 weeks from drawing approval, depending on panel size and switchgear availability.

Does Accu-Panels export LT panels?

Yes. Accu-Panels supplies CE-marked LT panels to more than 10 countries, including Africa and the Middle East, with sea-worthy packing and documentation.

Send your SLD. We'll design your LT panel.

Share the six inputs above and our engineers will return a GA drawing, bill of materials and techno-commercial offer.

Get LT panel offerCall +91 63588 01780