Quality and Certifications
- Home
- Quality
Quality report · Accu-Panels Energy
Electrical panel quality control you can verify
Every Accu-Panels LT panel, whether power, control, solar or EV, is built to a written Quality Assurance Plan, inspected at three stages and routine-tested to IEC 61439 before it leaves the factory. Nothing ships without a signed test certificate.
- 100% of panels routine-tested before dispatch
- 3-stage inspection: incoming, in-process, final
- CPRI type-tested design to IEC 61439-1/2
- IP65 & IP66 outdoor panels built on order
01
Four pillars of our quality
Certified system
ISO 9001:2015 quality management and MSME ZED practices run every department.
Every panel tested
Eight routine checks to IEC 61439-1, recorded on a signed certificate.
Built to protect
IP42 indoor panels up to IP65 and IP66 outdoor builds, with measured coating.
Traceable records
Registers at each stage, ERP-based tracking and documents that ship with the panel.
02
Our quality policy
Accu-Panels Energy Pvt. Ltd. designs and manufactures LT electrical panels known for lasting quality and good workmanship. We commit ourselves:
- Customer satisfaction. To reach and hold 100% customer satisfaction by continually improving product quality and on-time delivery, and by cutting internal rejection and waste.
- Infrastructure. To keep improving our plants and facilities so the company can grow faster and serve customers better.
- People. To build the skills of our team, so individual and team performance improves and quality becomes part of our culture.
- Compliance. To meet all applicable legal and statutory requirements.
- Review. To review our quality management system at regular intervals and keep improving it.
Managing DirectorAccu-Panels Energy Pvt. Ltd. · Shared with, and understood by, everyone in the company.
03
Certifications and capabilities
Copies of our certificates and the CPRI type-test report are shared with every techno-commercial offer on request.
04
Three-stage inspection
A panel is only as good as the parts inside it and the way they are put together. Select a stage to see what we check.
Incoming inspection
- Switchgear, meters, CTs, terminals and glands checked against the PO and BOM for make, rating and quantity
- CRCA sheet and wires checked visually and with vernier and wire gauge
- CTs given injection and polarity checks
- Anything that does not match goes back through purchase
Record · Material inward and incoming inspection register
In-process inspection
- 100% of fabricated parts measured for length, width, height and sheet thickness against the drawing
- Parts checked again before painting; coating thickness and shade checked after
- Busbar dimensions checked against the switchgear rating
- Assembly, door, handle and interlock alignment checked on the shop floor
Record · Production and in-process inspection register
Final inspection
- Full routine test procedure on every panel
- Final check of quantity, specification and finish against the order
- Panels that fail are held in the non-conformity area
- Only panels that pass are released for packing and dispatch
Record · Final inspection report and routine test certificate
05
Routine tests on every panel
These eight checks follow IEC 61439-1, clause 11. Tap a test to see how it is done.
01Degree of protectionPASS
Enclosure, gaskets, gland plates and door seals checked against the specified IP rating.
02Clearances and creepagePASS
Distances verified against the design values for the rated insulation voltage.
03Mechanical operationPASS
Breakers, interlocks, drawout mechanisms and doors operated and checked.
04Wiring and functionPASS
Point-to-point wiring check against the approved schematic, ferrule and label audit, functional, interlock and two-lamp continuity tests.
05Dielectric (HV) testPASS
2.5 kV AC for 1 minute between live parts and earth, and between phases.
06Insulation resistancePASS
500 V / 1000 V megger test before and after the HV test. Minimum 1 MΩ per circuit.
07Torque auditPASS
Busbar and terminal bolts checked to the manufacturer's torque table and marked.
08Protective circuit continuityPASS
Earth continuity checked to every door and compartment.
06
Additional in-house tests
Added as the panel type and the client's QAP require.
| Test | What we check |
|---|---|
| Mechanical endurance | Repeated closing and opening of ACBs, SFUs, MCCBs and MCBs; every interlock and tripping mechanism |
| Primary and secondary injection | Relays, releases and CT circuits, with CT polarity |
| HV, isolator open and closed | Between phases and to the earth busbar, with the isolating switch in both positions |
| Control circuit simulation | Feeder operations, remote indication lamps and remote controls |
| Pick-up and drop-out | Voltages for shunt-trip and closing coils |
| RS-485 / Modbus | Meter and relay communication tested with software |
| Client QAP extras | Phase sequence and clearance measurements with photographs, when asked |
07
Coating and enclosure protection
Powder coating, measured
Surface preparation is checked visually, thickness with a DFT meter and shade against a shade card, usually RAL 7035.
For coastal and very humid sites, read our C5 coating guide.
IP rating, built to the site
We build panels from IP42 for clean indoor rooms up to IP65 and IP66 for outdoor, dusty and wash-down areas.
| Code | Dust | Water |
|---|---|---|
| IP42 | Objects over 1 mm | Dripping water |
| IP54 | Dust-protected | Splashing water |
| IP55 | Dust-protected | Water jets |
| IP65 | Dust-tight | Water jets |
| IP66 | Dust-tight | Powerful water jets |
IP codes as defined in IEC 60529.
08
Testing instruments and calibration
Every instrument used for acceptance is calibrated on schedule, so a reading on our certificate means the same at your site.
- HV test set
- Megger
- Multimeter
- Series lamp
- Torque wrench
- DFT meter
- Shade card
- Vernier calliper
- Measuring tape
- Wire gauge

09
QAP and witnessed inspection
Our QAP lists each check, how much is checked, the acceptance rule, the record and the instrument. We also work to the QAP of EPC contractors and solar developers.
| QAP stage | Accu-Panels | Client | TPIA |
|---|---|---|---|
| Fabrication and pre-paint inspection | P | R | W |
| Switchgear, busbars and bought-out items | P | R | W |
| Surface cleaning and powder coating | P | R | W |
| Power charging and final testing | P | R | W |
P = perform · R = review · W = witness
Every panel ships with
- Routine test certificate
- Warranty certificate
- Approved drawings
- Bill of materials

10
When something is not right
- HoldA failed part or panel goes to the non-conformity area, so it cannot be dispatched by mistake.
- Find the causeFor critical failures we stop, find the root cause and fix it before work restarts.
- ImproveQuality, cost and delivery are reviewed every morning, defect trends every month, under our ZED practices.
11
Build quality commitments
A well-built panel lowers the risk of fire, equipment failure and costly shutdowns, and stays ready for tomorrow's loads.
- MaterialMild steel and CRCA with anti-corrosive powder coating; stainless steel for special environments.
- StructureWelding, sheet thickness and frame strength inspected for a rigid, damage-resistant enclosure.
- ComponentsCopper busbars, and switchgear from globally trusted brands such as ABB, Schneider Electric and Siemens.
- LayoutLogically arranged, clearly labelled components for safe operation and quick fault-finding.
- ProcessERP systems and SOPs give traceability and consistency across every department.
- ProtectionIP42 to IP66 enclosures, matched to the site.
12
After-sales support and client trust
13
Frequently asked questions
What tests are done on every electrical panel?
Eight routine checks under IEC 61439-1 clause 11, including the dielectric test, insulation resistance, torque audit, wiring and function checks, and earth continuity. Results go on a signed routine test certificate.
Do you build IP65 and IP66 panels?
Yes. We build panels from IP42 for indoor rooms up to IP65 and IP66 for outdoor, dusty and wash-down areas, on order.
Can our team or a TPIA witness the inspection?
Yes. Clients, consultants and third-party inspection agencies can witness the factory acceptance test, to our QAP or to your project QAP.
Which certifications does Accu-Panels hold?
ISO 9001:2015 (TÜV SÜD), MSME ZED, CPRI type tests to IEC 61439-1/2, an ASTA certificate from Intertek, and CE marking for export panels.
How thick is the powder coating?
60–80 microns DFT for standard indoor panels and 80–120 microns for outdoor, solar and coastal panels, measured with a DFT meter.
What documents come with the panel?
A routine test certificate, warranty certificate, approved drawings and the bill of materials. Explore our PCC, MCC and 800 V LT panel ranges.
14
Certificate gallery
Factory acceptance test
Witness your panel's tests
Your engineers, consultants or TPIA are welcome at our factory. Ask us for certificate copies, our QAP or a test date.