Solar ACDB and DCDB: How They Work in a Solar Power Plant

  • Home
  • Blog
  • Solar ACDB and DCDB: How They Work in a Solar Power Plant
Image

Every grid-connected PV plant has two switching points that decide whether a fault stays small or reaches the inverter. One sits on the DC side, where strings are combined; the other sits on the AC side, where inverter output meets the load and the grid. Both are distribution boards, and both are built to the same assembly standard as any other LT panel.

This article explains how solar ACDB and DCDB panels work in a solar power plant: where each board sits in the single-line diagram, which protective devices it carries, how enclosures are chosen for indoor and outdoor duty, and the standard input/output configurations used from rooftop systems to multi-megawatt plants. It is written for plant engineers, EPC estimators and consultants who specify these boards.

Figures reflect published standards and product documentation as of November 2026.

Key facts at a glance

  • DCDB configurations: 1 in/1 out to 10 in/10 out
  • ACDB range: 1 in/1 out (10 kW) to 20 in/1 out (10 MW, 4,000 A)
  • Indoor enclosure: IP52, 1.6 or 2 mm CRCA
  • Outdoor enclosure: IP65 CRCA; IP65/IP67 polycarbonate up to ~30 kW
  • Assembly standard: IS/IEC 61439-1, -2 or -3

Where solar ACDB and DCDB sit in the plant

A grid-connected PV system is a chain: PV array, string cables, DC distribution board (DCDB) or array junction box, inverter, AC distribution board (ACDB), and then the load bus or the grid interface. The DCDB collects several PV strings into one or more array outputs and protects the DC cables and the inverter from string faults and lightning surges. The ACDB takes the inverter output, provides isolation and overcurrent protection, meters the generated energy and distributes the power to loads or to the point of common coupling.

On a rooftop plant the two boards are wall-mounted boxes; on a megawatt plant the DC side is handled by string combiner boxes at the array and the AC side by a floor-standing LT panel. The functions do not change; only the ratings and the enclosure do.

What a DCDB does

The DC distribution board combines the DC output of several PV strings. Each string enters through a dedicated DC fuse so that a reverse-current fault in one string cannot be fed by the others. A DC surge protective device is connected between positive, negative and earth, and a DC isolator or DC MCB gives a visible break for inverter maintenance. Because strings remain live in daylight, the board is labelled to warn that it carries voltage after the inverter is isolated.

  • gPV-class DC fuses, one per string pole, rated for the system voltage (1,000 V or 1,500 V DC)
  • DC surge protective device, Type 2 on the array side, Type 1+2 where the lightning-protection study calls for it
  • DC switch-disconnector or DC MCB with the required DC breaking capacity and pole arrangement
  • MC4-type connectors or PG glands for string cables; a separate gland for the array output cable
  • Earth bar bonded to the enclosure and to the module frames

A string cable rated for at least 1.25 times the string short-circuit current needs no overload protection; the string fuse is chosen to protect against reverse current.

What an ACDB does

The AC distribution board sits between the inverter and the load or grid connection. It gives the inverter output a protected path, a point of isolation and an energy meter. Where several inverters feed one plant, the ACDB also parallels them on one busbar.

  • Incoming protection per inverter: MCB for small units, MCCB or fuse-switch for larger units, with breaking capacity above the prospective fault current at the point of connection
  • Outgoing MCCB or ACB on the load or grid side, sized for the sum of inverter output currents
  • AC surge protective device, Type 2, between each phase, neutral and earth
  • Switch-disconnector giving a visible break for the inverter installer
  • Multi-function energy meter (kWh, current, voltage, power factor), with CTs above direct-connection limits
  • Residual-current protection where required; an inverter without simple separation between DC and AC sides generally calls for a Type B device unless it is declared incapable of feeding DC fault current

Enclosures and ingress protection

Indoor boards are commonly built to IP52 in 1.6 mm or 2 mm CRCA sheet steel, seven-tank pre-treated and powder coated. Outdoor boards are built to IP65 in sheet steel with gasketed doors, canopies and bottom cable entry. For rooftop plants up to roughly 30 kW, IP65 or IP67 polycarbonate enclosures are common: corrosion-free, non-conductive and light enough for wall mounting.

Under IEC 60529 a second numeral of 7 (temporary immersion) does not by itself imply protection against water jets (numeral 5 or 6); an enclosure that must resist both is dual-coded, for example IP65/IP67.

Location Typical enclosure IP code Mounting
Indoor 1.6 or 2 mm CRCA, powder coated IP52 (IP54 with filtered vents) Wall or floor standing
Outdoor, near array 2 mm CRCA with canopy and gaskets IP65 Floor or stand mounted
Rooftop up to ~30 kW Polycarbonate, transparent door IP65 or IP65/IP67 Wall mounted

Standard configurations

Boards are described by the number of inputs and outputs. A 4 in / 4 out DCDB serves four strings feeding four MPPT inputs; on the AC side the inputs equal the number of inverters and the output is the single feeder to the load bus or grid panel.

Board Configuration Typical plant size Main device
DCDB 1 in / 1 out, 2 in / 2 out, 4 in / 4 out 1 to 30 kW rooftop DC fuse + DC isolator
DCDB 8 in / 8 out, 10 in / 10 out 30 to 250 kW DC fuse per string, DC SPD
ACDB 1 in / 1 out, 2 in / 1 out Up to 10 kW MCB, Type 2 SPD, meter
ACDB 3 in / 1 out Up to 25 kW MCB or MCCB per inverter
ACDB 4 in / 1 out Up to 200 kW MCCB per inverter, MCCB outgoing
ACDB 5 in / 1 out, 6 in / 1 out Up to 500 kW MCCB incomers, ACB or MCCB outgoing
ACDB LT panel 7 in / 1 out to 20 in / 1 out 500 kW to 10 MW, up to 4,000 A MCCB incomers, ACB outgoing, busbar

A typical specification for a mid-size plant reads: solar ACDB and DCDB panels with DC fuses, DC SPD and DC isolators on the array side, and MCCB incomers, Type 2 AC SPD and multi-function metering on the AC side, in IP52 indoor or IP65 outdoor enclosures. Above about 500 kW the ACDB becomes a floor-standing LT panel with an ACB outgoing and a busbar sized by temperature-rise verification.

Which standards apply

Both boards are low-voltage switchgear and controlgear assemblies built to IS/IEC 61439-1, with IEC 61439-2 for floor-standing ACDB LT panels or IEC 61439-3 for small boards operated by ordinary persons. An assembly is design-verified (by test, by comparison with a tested reference design, or by assessment) and every unit receives routine verification. In India a board is often called “type-tested” when its design verification was by test at a laboratory such as CPRI; the term is shorthand for a design verified by test.

Device standards sit underneath: IEC 60269-6 for gPV fuses, IEC 61643-11 and -31 for AC and DC surge protective devices, IEC 60947-2 and -3 for MCCBs and switch-disconnectors, and IEC 60529 for the IP code. Installation rules come from IEC 60364-7-712 (2017 edition) and, in India, from CEA regulations and DISCOM net-metering conditions. Leading international manufacturers publish combiner application notes that make the same points: string fusing against reverse current, Type 2 SPD close to the inverter, and DC switching rated for the full array voltage.

Frequently asked questions

Is a DCDB the same as an array junction box?

They perform the same function of combining and protecting PV strings. “Array junction box” or “string combiner box” is the usual name at the array on large plants; “DCDB” is the usual name for the board near the inverter on rooftop systems.

Does the ACDB need a surge protective device if the inverter has one built in?

Usually yes. The inverter’s internal SPD protects its own terminals; a Type 2 SPD in the ACDB protects the metering, the outgoing breaker and the downstream installation, and most DISCOM connection specifications require it.

Which IP rating should a rooftop ACDB have?

For an outdoor rooftop position, IP65 is the common minimum. IP67 alone does not guarantee resistance to water jets; specify IP65/IP67 if both are needed.